G18 15kV Make & Break Load Switching Relay 15 kv relay  
 Make & Break Load Switching (see ratings below)
 RoHS Compliant, date code 0701 and later
 
G18 HIGH VOLTAGE RELAY

G18 HIGH VOLTAGE RELAY
 



G 18
 
 

High Voltage Relay Features
  Durable tungsten contacts for hot load switching.
  Internal dielectric shield provides superior hot switch ratings.
  Vacuum dielectric for effective arc quenching when opening under load.
  Two mounting styles available, flange or through panel with jam nut.
  Solder or threaded high voltage connections help make installation easy.
  User interchangeable coils provide for driver versatility.
  Meets or exceeds standards set in MIL-R-83725.
High Voltage Relay Specifications
 Contact & Relay Ratings Units G18
 Contact Form C
 Contact Arrangement SPDT
 Voltage, Test Max., Contacts & to
 Base (15 µA Leakage  Max., dc or 60Hz)
kV Peak 17
 Voltage, Operating Max., Contacts & to
 Base (15 µA  Leakage Max.)
      dc or 60 Hz kV Peak 15
      2.5 MHz kV Peak -
      16 MHz kV Peak -
      32 MHz kV Peak -
 Current, Continuous Carry Max
      dc or 60 Hz Amps 30
      2.5 MHz Amps -
      16 MHz Amps -
      32 MHz Amps -
 Coil Hi-Pot (V RMS, 60 Hz) V 500
 Capacitance
      Across Open Contacts pF 0.5
      Contacts to Ground pF 1
 Resistance, Contact Max @ 1A, 28 Vdc ohms 0.025
 Operate Time ms 15
 Release Time ms 9
 Life, Mechanical cycles 1 million
 Weight, Nominal g (oz) 84 (3)
 Vibration, Operating, Sine (55-500  Hz  Peak) G's 10
 Shock, Operating, 1/2 Sine11ms (Peak) G's 50
 Temperature Ambient Operating °C -55 to +125


High Voltage Relays - Coil Ratings
 Nominal, Volts dc 12 26.5 115
 Pick-up, Volts dc, Max. 8 16 80
 Drop-Out, Volts dc .5 - 5 1 - 10 5 - 50
 Coil Resistance
 (Ohms  ±10%)
48 180 2900
Ratings listed are for 25°C, sea level conditions
 
For more information, refer to
Relay User Instructions

 
G18 S F  - 12Vdc

 High Voltage/
Power Terminal
Connections

 S = Solder Pot
 W = Screw

 Mounting 
 F
= Flange
 P = Through Panel
 Coil Voltageasteriks
 Blank = 26.5 Vdc
 12Vdc = 12 Vdc
 115Vdc = 115 Vdc


asteriks Order the relay with the coil voltage in the part number as shown above. The coil voltage will appear on the coil plate near the coil terminals rather than in the P/N on the relay.

SWITCHING UNDER LOAD

500V and below: Relay may be on either side of the load and the case may be floating or grounded.
See High Voltage Relay Grounding Requirements for details.

Above 500V: The relay must be on the ground side of the load and the case MUST be grounded.
See High Voltage Relay Grounding Requirements for details.

Make & Break Ratings
DC Voltage Current (Amps) Load Life (Cycles)
330 17 10,000
330 5 100,000
5kV 2 100,000
10kV 1 50,000

Contact GIGAVAC for Normally open Contact ratings.

04/03/08

GIGAVAC HV Relays GIGAVAC® - P.O. Box 4428 - Santa Barbara, CA 93140-4428 - ph +(805) 684-8401 - +(805) 755-2000  