G13L 15kV Latching Make Only Load Switching Relay 15 kv relay  
 Make Only Load Switching
 
G13 Latching hv relay


 




 
 

High Voltage Relay Features
  Latching coils for low power consumption and to ensure relay will remain in last position, even when no voltage is applied to the coil
  2 pole, Double Throw for switching between and/or reversing power sources or loads.
  Completely sealed for years of failure free operation.
  SF6 gas filled for high energy in-rush switching. asteriks
  Insulated flying leads make connection easy. Custom lengths available.
  Not position sensitive allowing mounting flexibility.
  Threaded base and top tabs provide mounting flexibility.
asteriks Consult factory for load switching applications.
 
High Voltage Relay Specifications
 Contact & Relay Ratings Units G13L
 Contact Form 2C
 Contact Arrangement DPDT
 Voltage, Test Max., Contacts & to
 Base (15 µA Leakage  Max., dc or 60Hz)
kV Peak 17
 Voltage, Operating Max., Contacts & to
 Base (15 µA  Leakage Max.)
      dc or 60 Hz kV Peak 15
      2.5 MHz kV Peak -
      16 MHz kV Peak -
      32 MHz kV Peak -
 Current, Continuous Carry Max
      dc or 60 Hz Amps 10
      2.5 MHz Amps -
      16 MHz Amps -
      32 MHz Amps -
 Coil Hi-Pot (V RMS, 60 Hz) V 500
 Capacitance
      Across Open Contacts pF 0.5
      Contacts to Ground pF 1
 Resistance, Contact Max @ 1A, 28 Vdc ohms 1.0
 Operate Time ms 15
 Reset Time ms 9
 Life, Mechanical cycles 1 million
 Weight, Nominal g (oz) 140 (5)
 Vibration, Operating, Sine (55-500  Hz  Peak) G's 10
 Shock, Operating, 1/2 Sine11ms (Peak) G's 50
 Temperature Ambient Operating °C -55 to +85


High Voltage Relays - Coil Ratings
 Nominal, Volts dc 26.5
 Pick-up, Volts dc, Max. 16
 Reset, Volts dc 1 - 10
 Coil Resistance
 (Ohms  ±10%)
-
Ratings listed are for 25°C, sea level conditions.
Coils are polarity sensitive.
Observe polarity marked on coil terminals.
 
 
For more information, refer to
Relay User Instructions

 
G13 L  -
 
Latching
Designator
 Coil Voltageasteriks
 Blank = 26.5 Vdc


asteriks Order the relay with the part number as shown. The latching "L" designator and the coil voltage will not appear in the P/N on the relay but will be indicated on the label that is on the base of the relay. Observe coil polarity.

 

04/03/08

GIGAVAC HV Relays GIGAVAC® - P.O. Box 4428 - Santa Barbara, CA 93140-4428 - ph +(805) 684-8401 - +(805) 755-2000  